For Healthcare

A clean bill of health for every hospital.

Noda works as a virtual building engineer across hospitals and health systems, cutting energy costs and emissions and catching faults in critical systems before they lead to failures.

Optimize condenser water setpointNeeds Acceptance$48,260/yr
$691K
Year 1 energy savings at one hospital of more than 700 beds
25%
Cut in energy use at the same hospital
89%
Performance to target after Noda, up from 67%

More of the budget back to patient care.

Noda lowers utility spend across hospitals, outpatient clinics, and medical office buildings, analyzing every site around the clock.

Bring chillers back to their design efficiency.

Hospital chiller plants run around the clock, and a chiller drawing more power per ton than its design figure costs money every hour. Noda's AI agents trace the gap to causes such as a fixed condenser water setpoint and write up each fix as a Project carrying its estimated annual savings.

Explore the Intelligence Layer
Insight
Condenser Water Setpoint Optimization Opportunity
CW Plant · Kestrel Ridge Medical Center
Condenser water setpoint85°FFixed
  • CH-1Design 0.58 kW/ton0.71 kW/ton
  • CH-2Design 0.58 kW/ton0.78 kW/ton
  • CH-3Design 0.58 kW/ton0.66 kW/ton

Lower HVAC costs across campus buildings.

Hospitals condition large volumes of outside air and reheat much of it at the zone. Noda finds heating that no space needs, from preheat valves leaking by to heat recovery running below its expected effectiveness.

Explore the platform
Insights 4Kestrel Ridge Medical Center
  • AHU Heat Recovery Lower than OptimalAHU-7 · Patient towerHigh
  • Preheat Valve LeakbyAHU-3 · Outpatient pavilionMedium
  • VAV Unnecessary HeatingVAV-214 · Administration buildingMedium
  • Hot water differential pressure optimization opportunityHW Plant · Central plantLow

One view across the whole health system.

Health systems run regional hospitals, outpatient clinics, and medical office buildings, with a mix of BMS vendors and equipment ages, often inherited through mergers. Noda brings every site into one model and one Project list, so facilities leaders can see which campuses hold the largest savings and where to send engineers first.

Explore Command Center
Project Overview
Building Priority Status
TitleBuildingPriority StatusImpact
Optimize CW setpoint
CW Plant
Kestrel Ridge Medical CenterHighNeeds Acceptance
0/3 Tasks
$48,260/yr
Balance chiller loading
CH-1, CH-2
Halloway Medical CenterHighIn Progress
1/3 Tasks
$17,940/yr
Restore heat recovery
AHU-7
Kestrel Ridge Medical CenterMediumIn Progress
2/4 Tasks
$21,380/yr
Lower static pressure
AHU-2
Kestrel Ridge NorthMediumCompleted
2/2 Tasks
$9,420/yr
Restore schedule
AHU-1
Halloway Medical PlazaLowNeeds Acceptance
0/2 Tasks
$3,870/yr

Measure progress on Scope 1 and 2 targets.

Cuts to boiler and steam use count toward Scope 1, and electricity savings toward Scope 2. Noda measures each completed Project against a weather-adjusted baseline and totals the reductions by hospital and across the system.

See Noda for sustainability teams
Closed ProjectsKestrel Ridge Health
Portfolio ViewBuilding View
Realized Savings$548,370
GHG Emissions Reduced1,284,610kgCO2e
Energy Saved3,962,480kWh
Projects Completed31
  • Johnson Controls
  • Honeywell
  • Siemens
  • Trane
  • Schneider Electric
  • Automated Logic
  • Distech Controls
  • Delta Controls
  • Tridium
  • Alerton

Works with the systems you already use.

Noda reads each hospital's BMS over BACnet/IP, Modbus, or MQTT through the Noda LaunchPad, a secure on‑premises gateway, and needs no new sensors.

Plant and air-side results from Noda customers

Sports & entertainmentCentral plantEnergy savings

$256,000 in annual savings from a 32% jump in plant efficiency.

What Noda Diagnosed

A new MLB stadium — with the largest single-panel retractable roof in the world — ran its condenser water plant at a fixed supply temperature, forcing chillers into low-efficiency operation with cooling tower fans pegged at 100%. A dynamic CWST reset tied to outside air conditions dropped plant efficiency from 0.91 to 0.59 kW/ton, a 32% gain.

3.2M kWh reduced over the season
0.91 → 0.59 kW/ton
32% efficiency gain
Dynamic CWST reset

Related reading

Frequently asked questions

  • Can Noda work in a hospital that runs 24/7?

    Yes. The Noda LaunchPad, a gateway on the hospital network, reads the trend data the BMS already records. Installation needs no shutdown, and the BMS keeps its existing programming.

  • Will Noda change ventilation in operating rooms or isolation rooms?

    Noda's recommendations go to the hospital's facilities team, and the team decides which to accept. Air change rates and pressure relationships in clinical spaces stay with the hospital's engineering and infection prevention teams.

  • Does Noda need access to patient data?

    No. Noda connects to building management systems, meters, and utility data, and none of those sources hold patient records.

  • Does Noda cover clinics and medical office buildings too?

    Yes. Outpatient clinics and medical office buildings sit in the same model as the hospitals. Many keep regular hours, so Noda also checks their air handlers against occupancy schedules.

AI that's always on call.

Continuous analysis for every site in a health system, every shift.

Get a demo